潔凈室FFU送風單元的常見故障分析與排除

2019-07-22 08:54:44 admin
潔凈室FFU送風單元的常見故障分析與排除
潔凈室FFU送風單元的常見故障分析與排除

一 氣流速度過低

1.通過電腦調大FFU的轉速百分比,以增大風機葉輪的輸出風量。

2.檢查電源是否為正確的電壓、電流和頻率。

3.如果氣流速度仍然很低,請更換HEPA/ULPA過濾器。

二 氣流速度過高

通過電腦調小FFU的轉速百分比,以減小風機葉輪的輸出風量。

三 氣流為非層流及/或雜質過多

1.確保在氣流通道的上游沒有大型的障礙物阻塞氣流。

2.判斷在同一清潔室或附近沒有其它氣流設備會影響氣流的正常流動。

3.檢查氣流速度,如果太低,則執行上文“氣流速度過低”中的步驟調大氣流。

4.對高效過濾器進行煙示氣流及光度計測試。必要時密封或更換HEPA/ULPA過濾器。 



  
?

關于我們

深圳市藍思凈化科技有限公司,致力于凈化行業十余年,是一家集空氣過濾器和凈化設備研發,生產與銷售的高科技企業,產品涵蓋各行業所需的空氣凈化設備及服務,包括對顆粒物(PM10,PM2.5,PM0.1)、病菌、氣態分子污染物(TVOC, 酸性,堿性氣體)等的評估和檢測,并提供全面有效的空氣凈化解決方案。公司從國外引進目前世界最先進的無隔板過濾器生產線及專有技術。可按GB/T 14295-2008國家標準,GB/T 13554-2008國家標準及國家GMP規范要求為生物制藥。。。。。